RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite1von11SeitenPage1of11pageserstellt:bju,13.
06.
2016Contents1.
GENERALINFORMATION,DISCLAIMER.
21.
1USB.
21.
2RS232.
21.
3RS485.
32.
STARTINGTHEPROGRAM.
42.
1ONLINEMODE,PARAMETRIZATION.
42.
1.
1BASICPARAMETERS.
42.
1.
2STARTMODBUSRTUCOMMUNICATION52.
1.
3APPLICATIONPARAMETEROFSENSOR.
52.
2ONLINEMODE,RECORD62.
2.
1SYSTEMCLOCK.
62.
2.
SYSTEMMEMORY.
63.
OPERATIONRLANET73.
1NORMALSTATE73.
2LEAKSTATE.
73.
3BREAKSTATE84.
PCSETTINGS95.
REVISION106.
APPENDIXI11RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite2von11SeitenPage2of11pageserstellt:bju,13.
06.
20161.
Generalinformation,DisclaimerThe"RLA_net_com"programrunsundertheWINDOWS7operatingsystem.
ItmaybecopiedtoanydirectoryonthePC.
Theprogramisstartedbydoubleclickingontheexe-file.
Thenfollowtheset-upprocedure.
WARNING:Iftheprogramisoperatedincorrectlyinonlinemode,itispossibletochangethesetofparametersontheconnected"RLAnet",andbydoingsotodisrupttheoperationalreliabilityoftheentireWaterWarningSystem!
Onlytrainedtechnicalstaffmayoperatetheprograminonlinemode.
DisclaimerBARTECGmbHshallnotassumeanyliabilityfordamageresultingfrominstallationanduseofthesoftware,andinparticularnoliabilityforpersonalinjuryordamagetopropertyandpecuniarylossrelateddirectlyorindirectlytouseofthesoftware.
UsingseveralRLAnetatRS485datacommunicationsnetwork,theinterfacetoapersonalcomputer(eventoitsUSB)canberealizedwithaRS485toUSBConverter.
RunningtheService-Software,thenodenumbercanbecalledorchanged.
Thetwisted-paircableoftheRS485-buscanbesetupto500m.
Alsoatstand-aloneoftheRLAnet,theRS485-buscanbeused,torungreaterdistancetocommunicatetoaPC.
Incaseofconnectingproblemsitcouldbenecessary,thatthePCinterfaceisassignedtoCOM1.
SeePoint4forfurtherdetails.
Thecomponents,BARTECactuallyprovide,aretheoneswhicharealreadyavailableforconnectingtheRLWmonitoringunit.
(seepoint1.
1to1.
3)Otherinterfacesmayalsobeoperable,e.
g.
:ADAM-45611.
1USBTheuseofanRS232toUSBadapterpermitsconnectionofthePCusingtheUSBinterface(assignmenttoCOM1likewisenecessary).
Thebrand"US232R-10"fromthecompanyFTDIChip(availablethroughRSComponents)hasbeentestedandworksperfectly.
BARTEC-ordercode386350(driverupdateviainternetatinstallation)1.
2RS232TheRS232cableconnectstotheRS485toRS232Converter(point1.
3).
BARTEC-ordercode386417(2mlength,housingnarrow)RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite3von11SeitenPage3of11pageserstellt:bju,13.
06.
20161.
3RS485UsingseveralRLAnetatRS485datacommunicationsnetwork,theinterfacetoapersonalcomputer(eventoitsUSB)canberealizedwithaRS485toRS232Converter.
ThebrandADAM-4520"fromthecompanyAdvantech(availableatConradElectronic)istestedandworksfine.
Set-upoftheDIP-switchesseebelow:BARTEC-ordercode232990ApowersupplyDC24Visnecessary.
Asuitablepowerpack,e.
g.
typeMDR-20fromthecompanyMeanWellcanbeprovidedbyBARTEC.
BARTEC-ordercode336448Wiringexample:RLAnetRS485ConverterRS232USBPC232990386417386350336448RLAnetPowersupplySW2:9600bps(default)SW1:10bits(default)RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite4von11SeitenPage4of11pageserstellt:bju,13.
06.
20162.
StartingtheprogramThe"RLA_net_com"programisstartedbydoubleclickingontheexe-file.
TheserialUSBinterfaceofthePCisused(seePoint1).
Initialscreenisshown:ItisrecommendedtoreadalsotheusermanualoftheRLAnetdeviceforproperunderstandingthefunctionofthewaterwarningsystem.
(downloadwww.
bartec.
de)2.
1Onlinemode,parametrizationThepurposeofthe"RLA_net_com"programistodemonstratethecommunicationinterfaceoftheBartec"RLAnet"WaterWarningSystemwithaPC.
TheprincipleoftheprogramisthattheusercansetthebasicparametersoftheRLAnet.
AlsotheapplicationparameteroftheexistentconnectedSensorwiring/lengthwillbesethereanduploadedtotheRLAnet.
2.
1.
1BasicparametersBasicparametersoftheRLAnetareplacedinabox"CommConfig"forsettingthecommunicationparametersofa)theserialportRS485.
Usethedrop-downmenuforselectingandclickthe"Set"-buttonforactivating.
Factorypre-set:-Serialnumber:COM1-Baudrate:9600b)theMODBUSRTU:Factorypre-set:-Address:1RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite5von11SeitenPage5of11pageserstellt:bju,13.
06.
20162.
1.
2StartMODBUSRTUcommunicationThereisareddot,signallingnocommunicationtoanexistingRLAnet.
Firstclickonthe"OpenSerial"button,toestablishthecommunication.
The"RLA_net_com"programsearchesforadevicewiththeaddress,showninthebox"Address".
Oncethehardwarewiringisokandasuitabledeviceisfound,thereddotturntogreen.
Iftheaddressdiffers,itisusefultosearchfordevices/addresses,whicharealreadywired.
Pressthe"Searchaddress"buttonandamessagegettingdisplayed.
Changingthefactorypre-setaddressontheRLAnet,typethedesiredaddressinthebox"NewAddress"andclickthe"Set"button.
TheaddressontheRLAnetwillgetchanged.
NohardwareDIP-switchesneeded.
WARNING:ChangingtheaddressinanexistingnetworkwithseveralRLAnetdevices,youwerepleasedtotakecareoftheapplicable"Waterwarningsystemdocumentation":EstablishorreviseanallocationmapwhichincludesadevicenamefortheRLAnet,Modbusaddress,locationwheremounted,warningletters,sensorparameters,…(seeexampleAppendixI)2.
1.
3ApplicationparameterofsensorTheapplicationparameteroftheexistentconnectedSensorwiring/lengthistobesetonthefollowingparameters:-Inductionlinelength:___m-Blackline:___OhmItisimportantforpreciselocationfunctiontosetthesetwoparametersinconclusionwiththedataoftheexistentSensor,connectedtotheRLAnet.
Factorypre-setparametersareobsolete.
Examples:a)30mofSCRsensorcableisconnected.
(ThenominalvalueoftheSCRis:6,0Ohm/m)-Inductionlinelength:30m;click"Write"button-Blackline:180Ohm(30m*6,0Ohm/m=180Ohm);click"Write"button-AsaresultoftheRLAnetinternalcalculation,thereisdisplayedthenominalvalue:6000mOhm/mb)30mofSCRsensorcableisconnectedandinseries2PSpointsensors(ThenominalvalueoftheSCRis:6,0Ohm/m)(ThenominalvalueofthePSis:60Ohm,represents10m)-Inductionlinelength:50m(30m+2*10m);click"Write"button-Blackline:300Ohm(30m*6,0Ohm/m+2*60Ohm=300Ohm);click"Write"button-AsaresultoftheRLAnetinternalcalculation,thereisdisplayedthenominalvalue:6000mOhm/mSensitivityparameterswererecommendedtoleaveasfactorypre-set!
-Leakupperlimit:120kOhm-Leaklowerlimit:1kOhm-ADCadjust:1000RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite6von11SeitenPage6of11pageserstellt:bju,13.
06.
20162.
2Onlinemode,record2.
2.
1systemclockTheRLAnetiscountingtimeanddate.
ForaproperrecordtableitisrecommendedtosettheRLAnetclocktotherealtime.
Usetheappropriateboxesandbuttons,asshown.
2.
2.
systemmemoryTheRLAnetisstoringupto32happeningsonitsmemory.
Thiscanbereadbyclickonthe"Readrecord"button.
Clearingthismemoryispossiblebyclickonthe"Clearrecord"button.
Thereportisreadableonly,ifthe"Monitoringmode"oftheserviceprogramisstopped.
WARNING:Anyinformationwhichhelpsaservicepersontofindoutleakagemessagesormalfunctionofthesystemshouldnotbedeleteduncareful.
RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite7von11SeitenPage7of11pageserstellt:bju,13.
06.
20163.
OperationRLAnetTheprogramcanbeoperatedbymouseclick.
Itprincipallyactsasaremoteconsolefortheactual"RLAnet"device.
WARNING:Theactuallyconnectedsensor/sensorlength/numberofpointsensorsmustcorrespondtotheloadedparameterdata!
Donotchangeapplicationparameter(seechapter2.
1.
3)withoutassignmentoftheoperatingcompany.
Itisalsoadvisabletothenchecktheprojectplanningdocuments.
Themonitoringmodeoftheserviceprogramrunsincaseofclickingthe"Startmonitor"button.
AmonitoringcycletimecanbeadjustedbysettingatimeinMillisecondsinthebox"Monitorperiod".
Factorypre-set:-Monitorperiod:1000msThereare3mainoperationstatesontheRLAnet.
1.
Normal2.
Leak3.
Break3.
1NormalstateGetthemonitormodestartedbyclicking"Startmonitor"button.
The"Normalstate"signalling,thatnoleakageisdetectedalongthesensorsandofcoursethewiringofthesensorsiswithoutfault.
Thecounterfor"Success"increases.
3.
2LeakstateGetthemonitormodestartedbyclicking"Startmonitor"button.
The"Leakstate"signalling,thataleakageisdetectedalongthesensors.
The"Leakposition"isbeingdisplayed,accuracyby1meter.
Thecounterfor"Success"increases.
Thecounterfor"Failure"remains.
WARNING:Ifthe"Confirmleakage"buttononcebeingclicked,theRLAnetisresetanditsdisplayisdeleted.
(Bypreventfromthisonprogramside,thisisonlypossibleincaseofstoppingthemonitormodebyclicking"Stopmonitor"button.
)OnlyServicepersonal,whoisinchargewiththefaultfindingandbuildingrepairshouldoperatethisbutton.
Straightafteroperationthisbutton,hemustgotothelocation,wheretheleakagewasdetectedandmusteliminateit.
TheRLAnetwillautomaticallyresettoNormalstate.
Onceeliminationisimmediatelynopossible,itishighlyrecommendedtore-starttheRLAnetbypower-offandpower-on!
Theleakagemessageisupcomingagain.
RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite8von11SeitenPage8of11pageserstellt:bju,13.
06.
20163.
3BreakstateGetthemonitormodestartedbyclicking"Startmonitor"button.
The"Breakstate"signalling,thatsensorsandofcoursethewiringofthesensorshasgotafault.
Thecounterfor"Success"increases.
Thecounterfor"Failure"remains.
Thestatecan'tbedeletedby"Confirmleakage"button.
Itwillbeself-deletedbyrepairofthefault.
RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite9von11SeitenPage9of11pageserstellt:bju,13.
06.
20164.
PCsettingsAdetaileddescriptionofthehardwareinterfaceoftheRLAnetcanbefoundinthechapter2.
2.
1.
Ifthe"plug&play"oftheUSBconverterdoesn'twork,itisusefultore-settheserialinterfaceofthePCtoport"COM1".
ItmustbepermanentlyassignedtothehardwareinterfaceRS232orUSBinthedevicemanageroftheWINDOWSoperatingsystem.
IfCOM1isalreadybeingused,thenthisinterfacemustbeassignedtoafreeCOMbeforehand.
RLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite10von11SeitenPage10of11pageserstellt:bju,13.
06.
20165.
RevisionThesoftware"RLA_net_com"releasesasfollow:Version:Dateofrelease:Comments:V0.
113.
06.
2016Betaversion,releasedV1.
012.
07.
2016ReleasedversionRLAnetWaterWarningSystemOperatinginstructionsforthe"RLA_net_com"V1.
0serviceprogramdated12.
07.
201620160712_bjuRLAnetParaSoftwareENrev_.
docxSeite11von11SeitenPage11of11pageserstellt:bju,13.
06.
20166.
AppendixIExampleforprojectplanningdocument,especiallyanapplicable"Waterwarningsystemdocumentation":Establishorreviseanallocationmapwhichincludese.
g.
devicenamefortheRLAnet,Modbusaddress,locationwheremounted,warningletters,sensorparameters,…RLAnetDevicenameModbusaddressLocation,wheremountedWarninglettersSensorparameter:"Inductionlinelength"Sensorparameter:"Blackline"LeakageerrorresponseChecked/revised[Date,sign]=A-10N1001BuildingNo.
1Room101LeakageServerroom10130m180mSwitchoffchiller;createalarmmessagetoservicepersonal=A-11N1002BuildingNo.
1Room102LeakageServerroom10220m120mSwitchoffchiller;createalarmmessagetoservicepersonal=A-12N1003BuildingNo.
1ServiceRoom110LeakageRoom11010m(1pointsensor)60mSwitchoffvalvecoldwaterpipe;createalarmmessagetofacilitypersonalWARNING:DonotchangetheaddressinanexistingnetworkwithseveralRLAnetdevices.
Youwerepleasedtotakecareoftheapplicable"Waterwarningsystemdocumentation".
乌云数据主营高性价比国内外云服务器,物理机,本着机器为主服务为辅的运营理念,将客户的体验放在第一位,提供性价比最高的云服务器,帮助各位站长上云,同时我们深知新人站长的不易,特此提供永久免费虚拟主机,已提供两年之久,帮助了上万名站长从零上云官网:https://wuvps.cn迎国庆豪礼一多款机型史上最低价,续费不加价 尽在wuvps.cn香港cera机房,香港沙田机房,超低延迟CN2线路地区CPU...
Pia云这个商家的云服务器在前面也有介绍过几次,从价格上确实比较便宜。我们可以看到最低云服务器低至月付20元,服务器均采用KVM虚拟架构技术,数据中心包括美国洛杉矶、中国香港、俄罗斯和深圳地区,这次春节活动商家的活动力度比较大推出出全场6.66折,如果我们有需要可以体验。初次体验的记得月付方案,如果合适再续约。pia云春节活动优惠券:piayun-2022 Pia云服务商官方网站我们一起看看这次活...
运作了18年的德国老牌机房contabo在继去年4月开办了第一个美国数据中心(中部城市:圣路易斯)后立马在本月全新上马两个数据中心:纽约、西雅图。当前,为庆祝美国独立日,美国三个数据中心的VPS全部免除设置费,VPS本身的配置很高,价格适中,有较高的性价比!官方网站:https://contabo.com/en/SSD VPSKVM虚拟,纯SSD阵列,不限制流量,自带一个IPv4内存CPUSSD带...
cn163.net为你推荐
招标文件采购方式:公开招标点击搜狗浏览器2excursionsios5微信群里正在组织赌博"2014年全国民营企业招聘会现场A区域企业信息",,,,FDCphpboxiphonex-routerX-Router这个软件有什么用phpechophp echo函数 是什么意思迅雷雷鸟迅雷会员每日免费抽奖,抽中迅雷的雷鸟披肩了,要钱吗
org域名 国外vps主机 双线vps 香港主机 12306抢票攻略 godaddy 轻博 论坛空间 丹弗 java虚拟主机 网通ip 个人空间申请 cpanel空间 上海域名 谁的qq空间最好看 ntfs格式分区 徐正曦 免费外链相册 独立主机 lamp的音标 更多